The power from the USB port is not enough to trip the breaker. To do a secondary injection trip test on insulated case circuit breakers, auxiliary power MUST be applied to the trip unit.Open breaker - this tests the mechanical functionality of the breaker and makes sure that when the trip unit tells the breaker to trip that the breaker will actually trip.The current sensor test does not test the pickup points like the secondary injection test does.Without this current sensor test, the only way to test the current sensors is to do a primary injection test.

Eaton galileo license software#
Eaton galileo license license#
You will need to generate a license request file from the computer the license will be for. Change In rating (for the insulated case circuit breakers only)Īll PXPM licenses are available for purchase at.There are three types of licenses available for purchase:

You will be prompted before a license is used. It includes 5 trials for testing the breaker and post-trip waveform capture. PXPM can be downloaded from has basic access to communicate with the PXR and read real time data. If the trip unit settings are not made using dials, the settings can be changed in PXPM and downloaded to the breaker. Once connected you can view settings and do secondary injection testing. You will need to use a micro-USB data cable to connect from a laptop to the trip unit. The Power Xpert Protection Management Software is used with the PXR trip units in the Power Defense insulated case circuit breakers and molded case circuit breakers. Industrial Control & Circuit Protection